True double-conversion online ups
High performance DSP technology guarantee
50Hz/60Hz frequency converter mode
Eco mode operation for energy saving (ECO)
Accepts dual power inputs
Emergency power off function(EPO)
Generator compatible
SNMP+USB-RS-232 mutiple communications
3-stage extendable charging design for optimized battery performance
Adjustable battery numbers
Maintenance bypass available
Optional N+X parallel redundancy
Standard online ups and online lead aircraft ups in one integrated unit
Model | 3/310K(S) | 3/315K(S) | 3/320K(S) | 3/330K(S) | ||
Phase | 3 phase in / 3 phase out | |||||
Capacity | 10000 VA/8000W | 15000V/12000W | 20000VA/16000W | 30000VA/24000W | ||
Input | Nominal Voltage | 3 x 400 VAC (3Ph+N) | ||||
Voltage Range | 305-478 VAC (3-phase) @ 100% load 190-520 VAC (3-phase) @ 50% load | |||||
Power Factor | ≥0.99 @ 100% load | |||||
Frequency Range | 46~54 Hz or 56~64Hz | |||||
Output | Output Voltage | 3 x 400 VAC (3Ph+N) | ||||
AC Voltage Regulation (Batt. Mode) | ± 1% | |||||
Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz | |||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |||||
Current Crest Ratio | 3:1 (max.) | |||||
Transfer Time | AC mode to Battery mode | zero | ||||
Inverter to Bypass | zero | |||||
Waveform (Batt. mode) | Pure Sine Wave | |||||
Efficiency | AC mode | 89% | 90% | |||
Battery mode | 86% | 88% | 87% | 89% | ||
Battery | Standard Model | Battery Type | 12 V / 9 AH | |||
Numbers | 20 pcs (18 - 20 adjustable) | 20 pcs (18 - 20 adjustable)x 2 strings | 20pcs (18-20adjustable)x 3 strings | |||
Typical Recharge Time | 9 hours recover to 90% capacity | |||||
Charging Current (max.) | 1A | 2A | 4A | |||
Charging Voltage | 273 VDC ± 1%(based on 20 pcs batteries) | |||||
Long-run Model | Battery Type | Depending on the capacity of external batteries | ||||
Numbers | ||||||
Charging Current (max.) | 4A | 12A | ||||
Charging Voltage | 273 VDC ± 1%(based on 20 pcs batteries) | |||||
Indicators | LCD Panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | ||||
Alarm | Battery Mode | Sounding every 4 seconds | ||||
Low Battery | Sounding every second | |||||
Overload | Sounding twice every second | |||||
Fault | Fault | |||||
Physical | Standard Model | Dimension, D X W X H (mm) | 815 x 250 x 826 | 815 x 300 x 1000 | ||
Net Weight (kgs) | 109 | 164 | 233.5 | |||
Long-run Model | Dimension, D X W X H (mm) | 592 x 250 x 826 | 815 x 250 x 826 | |||
Net Weight (kgs) | 38 | 40 | 64 | |||
Environment | Operation Humidity | 0-95 % RH @ 0- 40°C (non-condensing) | ||||
Noise Level | Less than 60dB @ 1 Meter | |||||
Management | Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and MAC | ||||
Optional SNMP | Power management from SNMP manager and web browser |